46-6 - DIN
Differential pressure regulators with flow limitation
USAGE
- Differential pressure and flow control
MEDIUM
Water and other liquids
Gases
VERSION
DIN
MEDIUM TEMPERATURE
2
to 150 °C /
35.6
to
302 °F
VALVE SIZE
DN 15
to
DN 50
PRESSURE RATING
PN 16
to
PN 25
FUNCTION
- Differential pressure limiter
- Flow limiter
APPLICATION
- Valve closes when the differential pressure rises
INSTALLATION
- Return flow pipe
FLOW RATE SET POINT
0.01 to 15 m³/h / 0.04 to 66 US gal/min
FLOW RATE DP ACROSS RESTRICTION
0.2 bar / 2.9 psi
DIFFERENTIAL PRESSURE SET POINT
0.2 to 2 bar / 2.9 to 29.01 psi
Special features
- Differential pressure regulators with flow limitation
- Consisting of valve with adjustable restriction and actuator with operating diaphragm
- Single-seated valve with balanced plug
- Particularly suitable for district heating systems according to DIN 4747-1
- Internal overload protection in the actuator